nday
CVE-2022-31207

The Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18…Title composed by nday; the CVE record has none.

Disclosed . nday has no fix record for it yet; that does not mean no patch exists. None of the four PoC sources lists it. Not in CISA KEV.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

cryptographic failure
CWE-347, stated by NVD's analysts
remote, unauthenticated
AV:N, PR:N, UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
network
AV:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no authentication required
PR:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no user interaction
UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
stage
DIS
disclosed
cvss
no score yet

Lifecycle

x axis UTC; dot = exact minute, wide bar = date only, hollow = unknown or inferred.
time unknown
DISdisclosed
2022-07-26T21:28Z
PATpatch
no record yet
ANAanalysis
no record yet
POCPoC
no record yet
ITWexploited
no record yet
KEVKEV
no record yet

Summary

The Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS (9600/TCP) protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication flaws as reported in FSCT-2022-0057. Control logic is downloaded to PLC volatile memory using the FINS Program Area Read and Program Area Write commands or to non-volatile memory using other commands from where it can be loaded into volatile memory for execution. The logic that is loaded into and executed from the user program area exists in compiled object code form. Upon execution, these object codes are first passed to a dedicated ASIC that determines whether the object code is to be executed by the ASIC or the microprocessor. In the former case, the object code is interpreted by the ASIC whereas in the latter case the object code is passed to the microprocessor for object code interpretation by a ROM interpreter. In the abnormal case where the object code cannot be handled by either, an abnormal condition is triggered and the PLC is halted. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, thus allowing an attacker to manipulate transmitted object code to the PLC and either execute arbitrary object code commands on the ASIC or on the microprocessor interpreter.

Original text of the CVE record (cvelist), shown as published.

Event log

+DISdisclosed

CVE record published by mitre.

src cvelist · nday , bulk import · raw
{
  "id": 266771,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2022-31207",
  "occurred_at": "2022-07-26T21:28:46Z",
  "observed_at": "2026-11-13T05:37:42.261111Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "state": "PUBLISHED",
    "date_published": "2022-07-26T21:28:46.000Z",
    "assigner_short_name": "mitre"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Researcher discussion

0 researchers mentioned this in the last 7 days

Posts on X by researchers on nday's list that mention this CVE, shown as posted. nday does not check them.

nday has not collected any post on X by listed researchers that mentions this CVE.

Discussion

0 comments

No comments yet.