nday
CVE-2022-31207

The Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18…Título compuesto por nday; el registro CVE no tiene título.

Fecha de divulgación: . nday aún no tiene constancia de una corrección; eso no significa que no exista parche. Ninguna de las cuatro fuentes de PoC la recoge. No figura en el KEV de CISA.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

cryptographic failure
CWE-347, stated by NVD's analysts
remote, unauthenticated
AV:N, PR:N, UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
network
AV:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no authentication required
PR:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no user interaction
UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
etapa
DIS
divulgación
cvss
sin puntuación aún

Ciclo de vida

Eje x en UTC; punto = minuto exacto, barra ancha = solo fecha, hueco = desconocida o inferida.
fecha desconocida
DISdivulgada
2022-07-26T21:28Z
PATparcheada
sin registro aún
ANAanalizada
sin registro aún
POCPoC
sin registro aún
ITWexplotada
sin registro aún
KEVen KEV
sin registro aún

Descripción

The Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS (9600/TCP) protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication flaws as reported in FSCT-2022-0057. Control logic is downloaded to PLC volatile memory using the FINS Program Area Read and Program Area Write commands or to non-volatile memory using other commands from where it can be loaded into volatile memory for execution. The logic that is loaded into and executed from the user program area exists in compiled object code form. Upon execution, these object codes are first passed to a dedicated ASIC that determines whether the object code is to be executed by the ASIC or the microprocessor. In the former case, the object code is interpreted by the ASIC whereas in the latter case the object code is passed to the microprocessor for object code interpretation by a ROM interpreter. In the abnormal case where the object code cannot be handled by either, an abnormal condition is triggered and the PLC is halted. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, thus allowing an attacker to manipulate transmitted object code to the PLC and either execute arbitrary object code commands on the ASIC or on the microprocessor interpreter.

Original text of the CVE record (cvelist), shown as published.

Registro de eventos

+DISdivulgación

mitre publicó el registro CVE.

fuente cvelist · nday , importación masiva · en bruto
{
  "id": 266771,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2022-31207",
  "occurred_at": "2022-07-26T21:28:46Z",
  "observed_at": "2026-11-13T05:37:42.261111Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "state": "PUBLISHED",
    "date_published": "2022-07-26T21:28:46.000Z",
    "assigner_short_name": "mitre"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Debate de investigadores

0 investigadores lo mencionaron en los últimos 7 días

Publicaciones en X de investigadores de la lista de nday que mencionan este CVE, tal como se publicaron. nday no las verifica.

nday aún no ha recopilado publicaciones en X de investigadores de su lista sobre este CVE.

Discussion

0 comments

No comments yet.