CVE-2022-30316

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data AuthenticityTitre composé par nday ; la fiche CVE n’en comporte pas.

Divulgation : . nday n’a encore aucune trace de correctif ; cela ne veut pas dire qu’il n’en existe pas. Cette vulnérabilité ne figure dans aucune des quatre sources de PoC. Aucune inscription au catalogue KEV de la CISA à ce jour.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

physical
AV:P in CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no authentication required
PR:N in CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no user interaction
UI:N in CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
étape actuelle
DIS
divulgation
CVSS
pas encore de score

Cycle de vie

Axe en UTC ; point = minute exacte, barre large = date seule, creux = inconnue ou déduite.
date inconnue
DISdivulguée
2022-07-28T15:41Z
PATcorrectif
aucune donnée
ANAanalyse
aucune donnée
POCPoC
aucune donnée
ITWexploitée
aucune donnée
KEVKEV
aucune donnée

Résumé

Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.

Original text of the CVE record (cvelist), shown as published.

Journal des événements

+DISdivulgation

Fiche CVE publiée par mitre.

source cvelist · importé en masse par nday le · brut
{
  "id": 266090,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2022-30316",
  "occurred_at": "2022-07-28T15:41:12Z",
  "observed_at": "2026-11-13T05:37:40.655522Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "state": "PUBLISHED",
    "date_published": "2022-07-28T15:41:12.000Z",
    "assigner_short_name": "mitre"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Échanges entre chercheurs

0 chercheur en a parlé ces 7 derniers jours

Publications sur X de chercheurs suivis par nday citant cette CVE, telles que publiées. nday ne les vérifie pas.

nday n’a encore recueilli aucune publication sur X d’un chercheur de sa liste citant cette CVE.

Discussion

0 comments

No comments yet.