nday
CVE-2021-27196

Specially Crafted IEC 61850 Protocol Sequence Vulnerability

揭露時間:。nday 尚未取得修補依據,不能據此認為沒有修補。四個 PoC 來源皆未收錄。目前未列入 CISA KEV。

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

remote, unauthenticated
AV:N、PR:N、UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA mitre
network
AV:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA mitre
no authentication required
PR:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA mitre
no user interaction
UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA mitre
目前階段
DIS
揭露時間
CVSS
7.5 HIGH v3.1

生命週期

橫軸 UTC;點=精確到分鐘,寬條=僅日期,空心=不明或推斷。
時間不明
DIS揭露
2021-06-14T21:20Z
PAT修補
尚無紀錄
ANA分析
尚無紀錄
POCPoC
尚無紀錄
ITW遭利用
尚無紀錄
KEVKEV
尚無紀錄

摘要

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.

Original text of the CVE record (cvelist), shown as published.

Exploit conditions

What an attack needs, read from the CVSS vector.
Attack vector AV:N
Network: the attacker only needs to reach it over the network
Attack complexity AC:L
Low: no special conditions; the attacker can expect repeatable success
Privileges required PR:N
None: no account or authorization needed
User interaction UI:N
None: no action by anyone other than the attacker

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CVSS 3.1 vector from the CVE record, scored by the CNA mitre.

事件紀錄

+DIS揭露

CVE 紀錄由 mitre 發布。CVSS 7.5,屬高風險等級。

來源 cvelist · nday 於 批次匯入 · 原始
{
  "id": 239916,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2021-27196",
  "occurred_at": "2021-06-14T21:20:38.696Z",
  "observed_at": "2026-11-13T05:37:21.680629Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "cvss": {
      "source": "cna",
      "vector": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
      "version": "3.1",
      "base_score": 7.5,
      "base_severity": "HIGH"
    },
    "state": "PUBLISHED",
    "date_published": "2021-06-14T21:20:38.696Z",
    "assigner_short_name": "mitre"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

研究員討論

近 7 天有 0 位研究員提及

名單內研究員在 X 上提及此 CVE 的貼文,照原文呈現,nday 不查核。

尚未收錄名單內研究員在 X 上提及此 CVE 的貼文。

Discussion

0 comments

No comments yet.