Unitronics VisiLogic before version 9.9.00, used in Vision and Samba PLCs and HMIs, uses a default administrative password. An unauthenticated attacker with network access can take administrative control of a vulnerable system.
{
"id": 729,
"type": "kev_added",
"source": "kev",
"url": "https://www.cisa.gov/known-exploited-vulnerabilities-catalog",
"occurred_at": "2023-12-11T00:00:00Z",
"observed_at": "2026-11-12T13:53:00.018191Z",
"is_backfill": true,
"dedupe_key": "",
"detail": {
"cwes": [
"CWE-1188"
],
"notes": "Note that while it is possible to change the default password, implementors are encouraged to remove affected controllers from public networks and update the affected firmware: https://downloads.unitronicsplc.com/Sites/plc/Technical_Library/Unitronics-Cybersecurity-Advisory-2023-001-CVE-2023-6448.pdf; https://nvd.nist.gov/vuln/detail/CVE-2023-6448",
"product": "Vision PLC and HMI",
"due_date": "2023-12-18",
"precision": "day",
"date_added": "2023-12-11",
"vendor_project": "Unitronics",
"forensic_triage": "No",
"required_action": "Apply mitigations per vendor instructions or discontinue use of the product if mitigations are unavailable.",
"vulnerability_name": "Unitronics Vision PLC and HMI Insecure Default Password Vulnerability",
"known_ransomware_campaign_use": "Unknown"
}
}