Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient…标题由 nday 生成;CVE 记录未提供标题。

披露于 。本站尚未获取修复依据,不能据此认为没有补丁。四个 PoC 来源都还没有收录。尚未列入 CISA KEV。

这些标签的依据

这些标签由 nday 按固定规则从下列事实自动推导,不是 NVD、编号分配方或其他来源给出的。全部标签和规则见 ~/tags。

远程未授权
NVD 分析人员 给出的 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H(CVSS 3.1)中的 AV:N、PR:N、UI:N
网络
NVD 分析人员 给出的 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H(CVSS 3.1)中的 AV:N
无需认证
NVD 分析人员 给出的 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H(CVSS 3.1)中的 PR:N
无需用户交互
NVD 分析人员 给出的 CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H(CVSS 3.1)中的 UI:N
当前阶段
DIS
披露
CVSS
暂无评分

生命周期

横轴 UTC;点=精确到分钟,宽条=仅日期,空心=未知或推定。
时间未知
DIS披露
2022-07-28T15:41Z
PAT补丁
尚无记录
ANA分析
尚无记录
POCPoC
尚无记录
ITW在野
尚无记录
KEVKEV
尚无记录

摘要

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

以上是 CVE 记录(cvelist)中的原文,未经改写。

事件记录

+DIS披露

CVE 记录发布,编号分配方是 mitre。

来源 cvelist · 本站 批量导入 · 原始记录
{
  "id": 266089,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2022-30315",
  "occurred_at": "2022-07-28T15:41:18Z",
  "observed_at": "2026-11-13T05:37:40.655522Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "state": "PUBLISHED",
    "date_published": "2022-07-28T15:41:18.000Z",
    "assigner_short_name": "mitre"
  }
}