nday
CVE-2022-2277

A vulnerability exists in the ICCP stack of the affected SYS600 versions due to validation flaw in the process that establishes the ICCP communication. The validation flaw will cause a denial-of-service when ICCP of SYS600 is request to forward any da ...

Hitachi Energy / MicroSCADA X SYS600

Disclosed . nday has no fix record for it yet; that does not mean no patch exists. None of the four PoC sources lists it. Not in CISA KEV.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

remote, unauthenticated
AV:N, PR:N, UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA Hitachi Energy
network
AV:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA Hitachi Energy
no authentication required
PR:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA Hitachi Energy
no user interaction
UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA Hitachi Energy
stage
DIS
disclosed
cvss
7.5 HIGH v3.1

Lifecycle

x axis UTC; dot = exact minute, wide bar = date only, hollow = unknown or inferred.
time unknown
DISdisclosed
2022-09-14T17:02Z
PATpatch
no record yet
ANAanalysis
no record yet
POCPoC
no record yet
ITWexploited
no record yet
KEVKEV
no record yet

Summary

Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

Original text of the CVE record (cvelist), shown as published.

Exploit conditions

What an attack needs, read from the CVSS vector.
Attack vector AV:N
Network: the attacker only needs to reach it over the network
Attack complexity AC:L
Low: no special conditions; the attacker can expect repeatable success
Privileges required PR:N
None: no account or authorization needed
User interaction UI:N
None: no action by anyone other than the attacker

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CVSS 3.1 vector from the CVE record, scored by the CNA Hitachi Energy.

Event log

+DISdisclosed

CVE record published by Hitachi Energy. CVSS 7.5, high.

src cvelist · nday , bulk import · raw
{
  "id": 255734,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2022-2277",
  "occurred_at": "2022-09-14T17:02:01.251Z",
  "observed_at": "2026-11-13T05:37:33.132383Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "cvss": {
      "source": "cna",
      "vector": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
      "version": "3.1",
      "base_score": 7.5,
      "base_severity": "HIGH"
    },
    "ssvc": {
      "timestamp": "2025-06-04T15:06:46.857674Z",
      "automatable": "yes",
      "exploitation": "none",
      "technical_impact": "partial"
    },
    "state": "PUBLISHED",
    "date_published": "2022-09-14T17:02:01.251Z",
    "assigner_short_name": "Hitachi Energy"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Researcher discussion

0 researchers mentioned this in the last 7 days

Posts on X by researchers on nday's list that mention this CVE, shown as posted. nday does not check them.

nday has not collected any post on X by listed researchers that mentions this CVE.

Discussion

0 comments

No comments yet.