nday
CVE-2020-24686

AC500 V2 webserver denial of service vulnerability

ABB / AC500 V2 products with onboard Ethernet

Disclosed . nday has no fix record for it yet; that does not mean no patch exists. None of the four PoC sources lists it. Not in CISA KEV.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

resource exhaustion
CWE-400, stated by the CNA ABB, NVD's analysts, and NVD, republishing [email protected]
remote, unauthenticated
AV:N, PR:N, UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA ABB
network
AV:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA ABB
no authentication required
PR:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA ABB
no user interaction
UI:N in CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (CVSS 3.1) from the CNA ABB
ICS / OT
affected products in the CVE record: ABB · AC500 V2 products with onboard EthernetCPE names NVD's analysts give as vulnerable: o:abb:pm554_firmware, o:abb:pm556_firmware, o:abb:pm564_firmware, o:abb:pm566_firmware, o:abb:pm572_firmware, o:abb:pm573_firmwarenday's type rule vendor:abb
stage
DIS
disclosed
cvss
7.5 HIGH v3.1

Lifecycle

x axis UTC; dot = exact minute, wide bar = date only, hollow = unknown or inferred.
time unknown
DISdisclosed
2021-02-26T15:10Z
PATpatch
no record yet
ANAanalysis
no record yet
POCPoC
no record yet
ITWexploited
no record yet
KEVKEV
no record yet

Summary

The vulnerabilities can be exploited to cause the web visualization component of the PLC to stop and not respond, leading to genuine users losing remote visibility of the PLC state. If a user attempts to login to the PLC while this vulnerability is exploited, the PLC will show an error state and refuse connections to Automation Builder. The execution of the PLC application is not affected by this vulnerability. This issue affects ABB AC500 V2 products with onboard Ethernet.

Original text of the CVE record (cvelist), shown as published.

Exploit conditions

What an attack needs, read from the CVSS vector.
Attack vector AV:N
Network: the attacker only needs to reach it over the network
Attack complexity AC:L
Low: no special conditions; the attacker can expect repeatable success
Privileges required PR:N
None: no account or authorization needed
User interaction UI:N
None: no action by anyone other than the attacker

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CVSS 3.1 vector from the CVE record, scored by the CNA ABB.

Event log

+DISdisclosed

CVE record published by ABB. CVSS 7.5, high.

src cvelist · nday , bulk import · raw
{
  "id": 226814,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2020-24686",
  "occurred_at": "2021-02-26T15:10:58Z",
  "observed_at": "2026-11-13T05:37:13.444896Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "cvss": {
      "source": "cna",
      "vector": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
      "version": "3.1",
      "base_score": 7.5,
      "base_severity": "HIGH"
    },
    "state": "PUBLISHED",
    "date_published": "2021-02-26T15:10:58.000Z",
    "assigner_short_name": "ABB"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Researcher discussion

0 researchers mentioned this in the last 7 days

Posts on X by researchers on nday's list that mention this CVE, shown as posted. nday does not check them.

nday has not collected any post on X by listed researchers that mentions this CVE.

Discussion

0 comments

No comments yet.