nday
CVE-2019-7225

The ABB HMI components implement hidden administrative accounts that are used during the…Title composed by nday; the CVE record has none.

Disclosed . nday has no fix record for it yet; that does not mean no patch exists. None of the four PoC sources lists it. Not in CISA KEV.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

hard-coded credentials
CWE-798, stated by NVD's analysts
adjacent network
AV:A in CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no authentication required
PR:N in CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
no user interaction
UI:N in CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H (CVSS 3.1) from NVD's analysts
ICS / OT
CPE names NVD's analysts give as vulnerable: o:abb:cp620-web_firmware, o:abb:cp620_firmware, o:abb:cp630-web_firmware, o:abb:cp630_firmware, o:abb:cp635-b_firmware, o:abb:cp635-web_firmware, o:abb:cp635_firmware, o:abb:cp651-web_firmware, o:abb:cp651_firmware, o:abb:cp661-web_firmware and 6 morenday's type rule vendor:abb
stage
DIS
disclosed
cvss
no score yet

Lifecycle

x axis UTC; dot = exact minute, wide bar = date only, hollow = unknown or inferred.
time unknown
DISdisclosed
2019-06-27T16:38Z
PATpatch
no record yet
ANAanalysis
no record yet
POCPoC
no record yet
ITWexploited
no record yet
KEVKEV
no record yet

Summary

The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.

Original text of the CVE record (cvelist), shown as published.

Event log

+DISdisclosed

CVE record published by mitre.

src cvelist · nday , bulk import · raw
{
  "id": 199595,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2019-7225",
  "occurred_at": "2019-06-27T16:38:39Z",
  "observed_at": "2026-11-13T05:36:54.581922Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "state": "PUBLISHED",
    "date_published": "2019-06-27T16:38:39.000Z",
    "assigner_short_name": "mitre"
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Researcher discussion

0 researchers mentioned this in the last 7 days

Posts on X by researchers on nday's list that mention this CVE, shown as posted. nday does not check them.

nday has not collected any post on X by listed researchers that mentions this CVE.

Discussion

0 comments

No comments yet.