nday
CVE-2015-5374

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module…Titre composé par nday ; la fiche CVE n’en comporte pas.

Preuve de concept publique parue 944 jours après la divulgation. nday n’a encore aucune trace de correctif ; cela ne veut pas dire qu’il n’en existe pas. Cette vulnérabilité figure dans 2 des 4 sources de PoC : exploitdb et metasploit. Aucune inscription au catalogue KEV de la CISA à ce jour.

why these tags

nday derives these tags by fixed rules from the facts below; NVD, the CNA and other sources do not assign them. Vocabulary and rules: ~/tags.

network
AV:N in AV:N/AC:L/Au:N/C:N/I:N/A:C (CVSS 2.0) from NVD's analysts
no authentication required
Au:N in AV:N/AC:L/Au:N/C:N/I:N/A:C (CVSS 2.0) from NVD's analysts
Metasploit
Metasploit modules auxiliary/dos/scada/siemens_siprotec4
Exploit-DB
Exploit-DB entries 44103

CVSS 2.0 has no user-interaction metric, so “no user interaction” and “remote, unauthenticated” are never assigned from a CVSS 2.0 vector.

étape actuelle
POC
divulgation
délai avant PoC
T+944d POC : date seule
CVSS
pas encore de score

Cycle de vie

Axe en UTC ; point = minute exacte, barre large = date seule, creux = inconnue ou déduite.
date inconnue
DISdivulguée
2015-07-18T10:00Z
PATcorrectif
aucune donnée
ANAanalyse
aucune donnée
POCPoC
2018-02-16, date seule
metasploit
ITWexploitée
aucune donnée
KEVKEV
aucune donnée

Résumé

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.

Original text of the CVE record (cvelist), shown as published.

Journal des événements

+DISdivulgation

Fiche CVE publiée par mitre.

source cvelist · importé en masse par nday le · brut
{
  "id": 68847,
  "type": "disclosed",
  "source": "cvelist",
  "url": "https://www.cve.org/CVERecord?id=CVE-2015-5374",
  "occurred_at": "2015-07-18T10:00:00Z",
  "observed_at": "2026-11-13T02:01:12.554432Z",
  "is_backfill": true,
  "dedupe_key": "",
  "detail": {
    "state": "PUBLISHED",
    "date_published": "2015-07-18T10:00:00.000Z",
    "assigner_short_name": "mitre"
  }
}
2018-02-16date seule, selon la source
+POCPoC publique

Exploit-DB recense un code d’exploitation public : « Siemens SIPROTEC 4 and SIPROTEC Compact EN100 Ethernet Module < 4.25 - Denial of Service » (EDB-44103).

source exploitdb 44103 · importé en masse par nday le · brut
{
  "id": 21428,
  "type": "poc_published",
  "source": "exploitdb",
  "url": "https://www.exploit-db.com/exploits/44103",
  "occurred_at": "2018-02-16T00:00:00Z",
  "observed_at": "2026-11-12T15:24:40.221206Z",
  "is_backfill": true,
  "dedupe_key": "44103",
  "detail": {
    "url": "https://www.exploit-db.com/exploits/44103",
    "file": "exploits/hardware/dos/44103.py",
    "kind": "exploit",
    "tags": [],
    "type": "dos",
    "title": "Siemens SIPROTEC 4 and SIPROTEC Compact EN100 Ethernet Module < 4.25 - Denial of Service",
    "author": "M. Can Kurnaz",
    "edb_id": 44103,
    "cve_ids": [
      "CVE-2015-5374"
    ],
    "platform": "hardware",
    "verified": false,
    "precision": "day",
    "confidence": "curated",
    "date_added": "2018-02-16",
    "date_updated": "2018-02-16",
    "date_published": "2018-02-16"
  }
}
date inconnuela source ne donne aucune date
+POCPoC publique

Metasploit propose le module auxiliary/dos/scada/siemens_siprotec4 (« Siemens SIPROTEC 4 and SIPROTEC Compact EN100 Ethernet Module - Denial of Service »). La source n’indique pas la date de publication du module.

source metasploit auxiliary/dos/scada/siemens_siprotec4 · importé en masse par nday le · brut
{
  "id": 49753,
  "type": "poc_published",
  "source": "metasploit",
  "url": "https://github.com/rapid7/metasploit-framework/blob/master/modules/auxiliary/dos/scada/siemens_siprotec4.rb",
  "occurred_at": null,
  "observed_at": "2026-11-12T15:24:51.477477Z",
  "is_backfill": true,
  "dedupe_key": "auxiliary/dos/scada/siemens_siprotec4",
  "detail": {
    "url": "https://github.com/rapid7/metasploit-framework/blob/master/modules/auxiliary/dos/scada/siemens_siprotec4.rb",
    "kind": "msf_module",
    "path": "/modules/auxiliary/dos/scada/siemens_siprotec4.rb",
    "rank": 300,
    "check": false,
    "title": "Siemens SIPROTEC 4 and SIPROTEC Compact EN100 Ethernet Module - Denial of Service",
    "cve_ids": [
      "CVE-2015-5374"
    ],
    "fullname": "auxiliary/dos/scada/siemens_siprotec4",
    "rank_name": "normal",
    "confidence": "curated",
    "module_type": "auxiliary",
    "module_last_modified": "2025-05-15 08:43:24 +0000",
    "vuln_disclosure_date": null
  }
}

Report an error

report an error or omission

Something on this page wrong or missing? Tell the editors; if they accept it, this page's revision log says so publicly. Upstream data is not changed.

Échanges entre chercheurs

0 chercheur en a parlé ces 7 derniers jours

Publications sur X de chercheurs suivis par nday citant cette CVE, telles que publiées. nday ne les vérifie pas.

nday n’a encore recueilli aucune publication sur X d’un chercheur de sa liste citant cette CVE.

Discussion

0 comments

No comments yet.